Valve Pressure + Temperature Relief 1000Kpa 15mm
PTR15‑1000‑LF pressure and temperature relief valve is designed to safely relieve excess pressure and temperature in hot water systems caused by thermal expansion or overheating. Rated at 1000 kPa with a 15mm (1/2") BSP connection, it discharges hot water to the drain line when required to protect the system. For improved efficiency and valve life, an expansion control valve (ECV) is recommended on the cold water supply, and a pressure limiting valve must be fitted if mains pressure exceeds 80% of the PTR set pressure. PTR and ECV valves are critical safety components and should be replaced every four years.
Stock Availability
- This item may not be stocked at all branches. Please contact your local branch for stock information.
- Where a Brand is not specified in the description, the item supplied may differ from the image shown. Variations may occur due to our chosen supplier at any given time.
- Please email info@swanonline.com.au if you require further information.